SX-200 ICP MX Technician’s Handbook
Rack mounting the controller or NSU
Use the Rack Mount Kit (Part Number: 50004150) to rack mount the
Controller. The NSU requires a different kit that is supplied with the unit.
1. Attach the brackets to the rack.
2. Slide the unit into the brackets.
3. Secure the unit to the brackets using the supplied thumbscrews. The
screws fasten to the underside of the unit and fit into the notch on the
bracket.
CAUTION:When installing the system in an enclosed rack, you
MUST provide adequate ventilation to ensure that the
maximum ambient temperature inside the rack does not
exceed 40°C/104°F.
CAUTION:Ensure that a hazardous condition does not result
from any uneven mechanical loading.
CAUTION:When using the system in a rack, you should
consider the connection of the equipment to the power supply
circuit and the effect that overloading of circuits might have on
overcurrent protection and supply wiring. When addressing
this concern, refer to the system’s ratings label.